Menu
Your Cart

INKNXDAL0640300 – industrial DALI-2 to KNX TP PRO gateway, 64 ECG devices + 8 DALI-2 sensors, 100–240 V AC/DC, 8 W, DIN-rail or wall mount

DALI-2 to KNX TP PRO Gateway – model INKNXDAL0640300 | Intesis by HMS
DALI-2 to KNX TP PRO Gateway – model INKNXDAL0640300 | Intesis by HMS
3 year warranty Quantity discount 5-7 days
DALI-2 to KNX TP PRO Gateway – model INKNXDAL0640300 | Intesis by HMS
DALI-2 to KNX TP PRO Gateway – model INKNXDAL0640300 | Intesis by HMS
INKNXDAL0640300 – industrial DALI-2 to KNX TP PRO gateway, 64 ECG devices + 8 DALI-2 sensors, 100–240 V AC/DC, 8 W, DIN-rail or wall mount
  • Stock: 5-7 days
  • Brand: Intesis
  • Model: INKNXDAL0640300
2,514.50 zł
2 pieces or more 2,388.78 zł
5 pieces or more 2,338.49 zł
10 pieces or more 2,263.05 zł
26 pieces or more 2,137.33 zł
51 pieces or more 1,911.02 zł

INKNXDAL0640300 – industrial DALI-2 to KNX TP PRO gateway, supporting up to 64 DALI ECG devices and 8 sensors, 100–240 V AC/DC power supply, 8 W consumption, DIN-rail or wall mount.

INKNXDAL0640300 is a high-performance Intesis DALI-2 to KNX TP PRO Gateway designed for lighting integration between DALI-2 networks and KNX TP systems. The device acts as a DALI-2 multi-master controller, enabling full control and monitoring of ECG devices, groups and broadcast functions. It supports standard ON/OFF and dimming commands as well as RGBW color control, tunable-white and emergency-lighting features compliant with EN 62386-202. Certified for both DALI-2 and KNX, the gateway ensures seamless interoperability in professional building-automation projects and multi-master operation.

The gateway supports up to 64 DALI electronic control gear (ECG) and 8 DALI-2 sensors, which can be controlled individually or grouped into 16 DALI groups. A built-in 15 V DC DALI bus power supply eliminates the need for an external supply for luminaires. The gateway supports Human-Centric Lighting (HCL) concepts such as dynamic white-temperature control, HSV color adjustment and x/y color-space settings. It also keeps operating-time logs and detects DALI bus errors to enhance maintenance and system reliability. These capabilities make it suitable for modern energy-efficient and human-focused lighting installations.

Configuration can be performed directly on the device (via buttons and LEDs), through ETS +DCA, or via the embedded web interface. The gateway supports KNX Data Secure, ensuring encrypted and authenticated communication within the KNX network. It also offers MQTT / IoT integration, allowing connection with cloud platforms and smart-building management systems. Additional features include support for physical and virtual input devices such as motion sensors, light sensors and wall push-buttons for advanced automation scenarios. All parameters can be easily backed up and restored through the Intesis web configuration tool.

The gateway is housed in a robust PC enclosure (72 × 90 × 58 mm, 157 g net weight) and is suitable for DIN EN60715 TH35 or wall mounting. It operates with a wide-range power supply of 100–240 V AC/DC, 50/60 Hz, with a maximum power consumption of 8 W. Galvanic isolation of 4 – 5.3 kV between KNX, DALI and supply circuits ensures safe and reliable operation in commercial and industrial environments. The operating temperature range is −5 to +45 °C, and storage range −25 to +55 °C, with humidity up to 95 % non-condensing. Each unit is supplied with a detailed installation manual and cable protection accessories.

Main features
  • Bidirectional DALI-2 ↔ KNX TP PRO communication certified by DALI and KNX associations.
  • Supports 64 ECG devices and 8 DALI-2 sensors, organised into 16 groups.
  • Integrated 15 V DC DALI power supply – no external bus supply required.
  • Full light control – RGBW, Tunable White, HSV and x/y Color Space.
  • Human-Centric Lighting (HCL) functionality for comfort and energy efficiency.
  • KNX Data Secure – encrypted and safe communication within KNX networks.
  • MQTT / IoT ready – connectivity to smart-building and cloud platforms.
  • Configuration via ETS +DCA, Web UI or local interface (button and LED).
  • Power supply 100–240 V AC/DC, consumption 8 W, isolation 4–5.3 kV.
  • Durable PC housing, DIN rail or wall mount, 3-year warranty.

Technical specifications

Ports and interfaces
  • DALI: 1 channel (64 ECG + 8 DALI-2 sensors), integrated 15 V DC bus supply.
  • KNX TP: 2-pin terminal connector, supports KNX Data Secure.
  • Ethernet: for configuration and web access; supports MQTT/IoT integration.
  • Power supply: 3-pin terminal (100–240 V AC/DC, 50–60 Hz).
  • LED indicators: status and communication for KNX and DALI interfaces.
Power and isolation
  • Input voltage: 100–240 V AC/DC, 50–60 Hz.
  • Power consumption: 8 W max.
  • Galvanic isolation: 4 – 5.3 kV between KNX, DALI and power sections.
Housing and mounting
  • Material: PC plastic, color RAL 7035 (light grey).
  • Dimensions: 72 × 90 × 58 mm; weight 157 g (net).
  • Mounting: DIN EN60715 TH35 rail or wall mounting.
Environmental conditions
  • Operating temperature: −5 to +45 °C; storage: −25 to +55 °C.
  • Humidity: up to 95 % non-condensing.
Certifications and standards
  • Certifications: DALI-2, KNX, CE (IT & Telecom Equipment – WEEE Category).
  • Country of origin: Germany; HS Code: 8517620000.
  • Warranty: 3 years.

Example of integration


General technical parameters
M-Bus master up to 64 slaves
Industrial grade
Operating temperature -5 °C to 45 °C
Input voltage 100~240VDC
Manufacturer's warranty 36 months
Mount DIN rail

Write a review

Note: HTML is not translated!
Bad Good
1

We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!

Do you have a question about a product? Write to us!

We use cookies to offer you the best experience on our site. By continuing to browse the site, You are agree to use cookies.