FLAME-X 950 (N)HXH FE180/E30 0,6/1 kV

FLAME-X 950 (N)HXH FE180/E30 0,6/1 kV
To be confirmed
FLAME-X 950 (N)HXH FE180/E30 0,6/1 kV
  • Stock: To be confirmed
  • Brand: TELE-FONIKA Kable
  • Model: FLAME-X 950 (N)HXH FE180/E30 0,6/1 kV
0.00 zł
A proven choice for industrial installations.
Ask for compatibility and model selection.
Register and get cheaper offers today.

Full design package: User manual, CE declaration, CAD, PDF, certificates and test reports

If you're preparing technical documentation or an installation design, you can receive a complete set of design materials for this model. This is a quick way to gather the required documents for audits, acceptance, or project documentation.

  • Device User Manual
  • CE Declaration of Conformity (EU Declaration of Conformity)
  • Mechanical DrawingsCAD (STEP/DWG) or high-quality PDF
  • Additional Certificates (if available for the model)
  • Test Reports (if available for the model)
Request a package: User manual, CE declaration, CAD, PDF, certificates, test reports

Fire-resistant safety cables, halogen-free with low smoke emission.

Halogen-free and fire-proof electric and signal cables are designed for applications where special protection of people, cultural and material assets is required. They ensure the functioning of warning systems, fire extinguishing, power emergency lighting, ventilation, smoke dampers and other, whose operation is necessary for the effective conduct of rescue operations.

Construction:

  • Veins: of annealed copper, round class 1 (RE) or circular round compaction class 2 (RM) or sector class 2 (SM) according to EN 60228
  • Insulation: Special cross-linked halogen-free compound
  • Filling coating: Special halogen-free halogen-free compound
  • Coating: Thermoplastic halogen-free HM4 material according to DIN VDE 0276-604
  • Coating color: orange
  • Core colors (according to DIN VDE 0293-308, HD 308 S2 or EN 50334):
    • (N) HXH-O FE180 / E30, without protective conductor:
      • 1-vein: black
      • 2-veins: blue, brown
      • 3-veins: brown, black, gray
      • 3-veins for specific applications: blue, brown, black
      • 4-veins: blue, brown, black, gray
      • 5-veins: blue, brown, black, gray, black
      • above 5-veins: black numbered
    • (N) HXH-J FE180 / E30, with protective sheath:
      • 1-vein: yellow-green
      • 3-veins: green-yellow, blue, brown
      • 4-veins: green-yellow, brown, black, gray
      • 4-veins for specific applications: yellow-green, blue, brown, black
      • 5-veins: green-yellow, blue, brown, black, gray
      • above 5-veins: yellow-green, the remaining veins are black numbered

Characteristic:

  • Maximum core temperature during cable operation: + 90 °C
  • Minimum ambient temperature for permanently laid cables: -40 °C
  • Minimum ambient temperature for cable laying: -15 °C
  • Maximum core temperature during short circuit: + 250 °C
  • The minimum bending radius:
    • 15D - for single-core cables
    • 12D - for multi-core cables
    • D - cable diameter
  • The maximum tensile force for copper conductors: 50 N / mm
  • Standard packaging: 500 or 1000m on drums. Other forms of packaging after agreement with the ordering party

Reaction to fire:

  • Resistance to fire FE 180: DIN VDE 0472-814 (800 ° C, 180 min.), IEC 60331-21
  • Retaining the functions of the E30 cable system: DIN 4102-12 (30 min.)
  • Resistance to flame spread: DIN EN 60332-1-2, DIN EN 60332-3-24
  • Fume emission during combustion: DIN EN 61034-2
  • Separation of corrosive gases during combustion:
    • DIN EN 60754-2, pH ≥ 4,3 & conductivity μ 10 mSmm²-1
    • DIN EN 60754-1, HCL ≤ 0,5%

Compliant with: DIN VDE 0266, DIN 4102-12

Certifications and approvals: GOST


Industrial grade
Operating temperatureto 90°C
Cable parameters
Minimum bending radius15D, 12D
CoreCopper
InsulationHalogen-free material (LSOH)
Installation temperature-15°C to 90°C
Maximum short circuit temperature250°C
Standard packagingOn drums
CoatingHalogen-free material (LSOH)
FillingHalogen-free material (LSOH)
Minimum ambient temperature-40°C
Resistance to flame spreadDIN EN 60332-1-2, DIN EN 60332-3-24
Fume emission during combustionDIN EN 61034-2
Number of wires in the cableSingle-core, Multi-core
Outer diameter [mm]6.2, 6.5, 7.0, 7.5, 8.3, 9.4, 9.8, 11.5, 12.6, 14.3, 15.6, 18.2, 19.6, 21.8, 23.9, 27.0, 29.4, 11.1, 11.9, 12.8, 13.8, 15.4, 19.0, 22.4, 11.6, 12.5, 13.4, 14.5, 16.2, 19.1, 20.0, 23.7, 26.0, 29.6, 33.3, 38.6, 41.8, 46.6, 51.1, 60.6, 24.9, 26.8, 31.1, 34.8, 40.5, 44.2, 48.1, 53.4, 60.3, 15.7, 17.6, 20.8, 25.9, 28.5, 33.2, 36.8, 42.7, 46.7, 51.8, 57.2, 64.6, 13.5, 17.1, 19.2, 22.6, 23.8, 28.4, 31.4, 40.6, 47.6, 51.5, 57.9, 63.4, 71.6, 17.0, 17.9, 18.5, 17.8, 18.6, 19.4, 20.4, 18.4, 19.9, 21.0, 20.1, 20.9, 22.0, 20.2, 21.1, 23.2, 21.2, 22.2, 23.1, 24.4, 23.3, 24.6, 25.8, 28.3, 27.2, 28.6, 30.2, 28.1, 29.5
Cable weight [kg/km]55, 66, 84, 106, 149, 213, 222, 326, 424, 561, 761, 1042, 1278, 1573, 1951, 2519, 3128, 175, 211, 260, 321, 437, 643, 682, 989, 196, 242, 304, 382, 532, 788, 831, 1219, 1567, 2072, 2830, 3846, 4692, 5791, 7138, 9495, 1395, 1753, 2375, 3219, 4393, 5466, 6541, 8172, 10542, 228, 283, 362, 460, 649, 967, 1016, 1500, 2651, 3581, 4873, 6009, 7378, 9170, 11810, 269, 337, 433, 556, 790, 1176, 1238, 1838, 2397, 3265, 4394, 6040, 7384, 9170, 11308, 14568, 320, 408, 534, 570, 693, 444, 472, 572, 610, 492, 521, 636, 679, 546, 579, 713, 759, 647, 799, 851, 684, 725, 903, 961, 752, 800, 853, 906, 1129, 1203, 1001, 1061, 1351, 1437, 1197, 1270