HD67712-IP-2-A1
3-4 days
Industrial BACnet IP master to RS-232 Modbus slave converter, housing type A (slim), DIN rail mount.
HD67712 is a BACnet Master / Modbus Slave Converter and it allows you to connect some BACnet slaves with a Modbus Master (for example a PLC, HMI). Converter is easy to configure thanks to free SW67712 software.
Configuration:
Thanks to the SW67712 software on your PC you can:
- Define the parameters of BACnet line
- Define the parameters of Modbus line
- Define the BACnet data that the converter reads/writes
- Update the device
Characteristics:
- Up to 512 BACnet objects in reading and 512 objects in writing
- Triple isolation between Serial - Power Supply, Serial - Ethernet, Ethernet - Power Supply
- Bi-directional information exchange between Modbus bus and BACnet bus
- Mountable on 35mm Rail DIN
Specifications:
- Ports: 2x Ethernet; 1x RS-232
- Serial protocol: Modbus slave
- BACnet protocol:Bacnet IP master
- Data Rates Serials: Up to 115200 bps
- Data Rates BACnet: 10/100 Base-T Autosensing
- Serials connector: 3way 5mm removable screw terminal
- BACnet connector: RJ45
- Power supply: 8 ~ 24V AC; 12 ~ 35V DC
- Power supply connector: 2way 5mm terminal block
- Operating temperature: -40°C to +85°C (-40°F to +185°F)
- Dimensions: 120 mm x 23 mm x 107 mm (DxWxH)
- Weight: 200g approx
- Mechanical fixing: 35mm DIN Rail mount
- Software: SW67712
- ORDER CODE: HD67712-IP-2-A1
Configurator – Software SW67712 FREE DOWNLOAD
General technical parameters | |
Ethernet | 2x 10/100BaseT(X) |
Serial port | 1x RS-232 |
Protocol support | BACnet IP, Modbus RTU |
Industrial grade | |
Operating temperature | -40°C to 85°C |
Input voltage | 8~24VAC, 12~35VDC |
Manufacturer's warranty | 24 months |
Mount | DIN rail |