Menu
Your Cart

INBACPAN001R000 Panasonic ECOi and PACi to BACnet gateway for BMS monitoring and control

INBACPAN001R000 is Panasonic ECOi and PACi to BACnet gateway for BMS monitoring and, temp. 0…40°C, DIN rail, cert UL/CE/ROHS.

INBACPAN001R000 - Panasonic ECOi and PACi to BACnet gateway for BMS monitoring and control
New 3 year warranty 5-7 days
INBACPAN001R000 Panasonic ECOi and PACi to BACnet gateway for BMS monitoring and control
  • Stock: 5-7 days
  • Brand: Intesis
  • Model: INBACPAN001R000
1 445,72 zł
2 pieces or more 1 373,43 zł
5 pieces or more 1 344,52 zł
10 pieces or more 1 301,15 zł
26 pieces or more 1 228,86 zł
51 pieces or more 1 098,75 zł
A proven choice for industrial installations.
Ask for compatibility and model selection.
Additional discounts for registered customers.

Full design package: User manual, CE declaration, CAD, PDF, certificates and test reports

If you're preparing technical documentation or an installation design, you can receive a complete set of design materials for this model. This is a quick way to gather the required documents for audits, acceptance, or project documentation.

  • Device User Manual
  • CE Declaration of Conformity (EU Declaration of Conformity)
  • Mechanical DrawingsCAD (STEP/DWG) or high-quality PDF
  • Additional Certificates and Test Reports (if available for the model)
Request a package: User manual, CE declaration, CAD, PDF, certificates, test reports

Panasonic ECOi and PACi air conditioner communication module for BACnet interface.

The IntesisBox INBACPAN001R000 interface is designed to integrate Panasonic ECOi and PACi air conditioning systems into building automation environments using BACnet (BACnet IP or BACnet MS/TP). It provides a clean, BMS-friendly way to expose HVAC functions as BACnet objects, so the AC system can be supervised and controlled alongside the rest of the building infrastructure.

Manufacturer code change
Old code: PA-RC2-BAC-1
New code: INBACPAN001R000
Technically identical product – only the name / SKU has changed.

The gateway supports bi-directional operation: it enables BMS-level control of key HVAC functions (such as operating mode, fan speed and temperature setpoint), and also returns feedback from the indoor unit. In practice, this means the BMS can react not only to user commands, but also to faults, alarms and selected internal variables, improving both comfort supervision and service visibility.

Commissioning is intentionally straightforward. INBACPAN001R000 can be installed and configured in a short time by wiring the gateway to the AC system and setting the required parameters using DIP switches. No dedicated configuration software and no external power supply are required. The device also includes a network interface for convenient monitoring and control of the connected indoor unit, and for setting IP network parameters directly from the same interface.

Technical specification

Specification:

Ports:

  • BACnet MS/TP port: 1x EIA485 2-pin screw terminal + GND
  • Console port: Mini USB

Terminal wiring (power and low-voltage signals):

  • At the terminal: solid or stranded wires (stranded or ferruled):
    • 1 core: 0.5mm2...2.5mm2
    • 2 cores: 0.5mm2...1.5mm2
    • 3 cores: not allowed

Isolation voltage:

  • 4000 VDC (between the AC module and EIA-485)
  • 1000 VDC (between the AC unit and the console)

Control and monitoring:

  • LED indicators: 6 x gateway / communication status

Mechanical:

  • Enclosure: Plastic, PC type (UL 94 V-0)
  • Dimensions: 93mm x 53mm x 58mm
  • Color: Light Grey
  • Protection rating: IP20 (IEC60529)
  • Mounting: Wall mount; DIN rail EN60715 TH35

Environmental:

  • Operating temperature: 0°C to 40°C
  • Humidity: 5% - 95%, non-condensing

Certificates & Standards:

  • CE compliance with EMC Directive (2004/108/EC) and Low Voltage Directive (2006/95/EC)
  • EN 61000-6-1
  • EN 61000-6-3
  • EN 60950-1
  • EN 50491-3
  • RoHS compliant: compliant with RoHS Directive (2002/95/EC)

Manufacturer warranty: 36 months