NA2XS(F)2Y
To be confirmed
Power cables with aluminum wires with XLPE insulation and PE coating.
Construction:
- Veins: Multi-round round class 2 according to EN 60228
- Screen on the veins: Semi-conductive polyethylene
- Isolation: Cross-linked polyethylene
- Screen on insulation: Semi-conductive polyethylene
- Sealing: Thrust
- Metallic screen: Cu wires / Cu band
- Coating: Polyethylene
- Coating color: UV-resistant red
Characteristic:
- Maximum core temperature during cable operation: + 90 °C
- Minimum ambient temperature for permanently laid cables: -30 °C
- The minimum ambient temperature for cable laying: -20 °C
- Maximum core temperature during short circuit: + 250 °C
- Maximum pull force for the work piece: 30 x S (S = cross-section Al in mm²) [N]
- Min. Bending radius: 15d (d = cable diameter)
- Test voltage: 3.5 * Uo / 5 min
- Application: For the transmission of electricity. They can be laid in the ground, indoors and outdoors.
- Packing: 500 or 1000 m on the drum. It is possible to offer other lengths and types of packaging
Compliant with: PN-HD-620 S2: 10C / DIN VDE 0276-620
Cable parameters | |
Core | Aluminium |
Insulation | XLPE |
Outer coating | Polyethylene, Polyvinyl chloride (PVC) |
Maximum allowable tensile stresses | 1.5 kN, 2.1 kN, 2.85 kN, 3.6 kN, 4.5 kN, 5.55 kN, 7.2 kN, 9.0 kN, 12.0 kN, 15.0 kN, 18.9 kN, 24.0 kN, 30.0 kN |
Diameter of the working conductor [mm] | 8.25, 9.5, 11.3, 12.5, 14.2, 15.8, 17.9, 20.0, 22.9, 25.7, 29.3, 33.0, 38.0 |
Outer diameter [mm] | 28.1, 29.4, 31.2, 32.4, 34.1, 35.7, 37.8, 39.9, 42.8, 46.3, 50.3, 54.6, 60.0, 30.1, 31.4, 33.2, 34.4, 36.1, 37.7, 39.8, 41.9, 44.8, 48.3, 52.3, 56.8, 62.0 |
Cable weight [kg/km] | 720, 890, 1100, 1330, 1440, 1580, 1780, 1990, 2300, 2710, 3190, 3780, 4510, 790, 970, 1180, 1420, 1540, 1680, 1890, 2110, 2420, 2840, 3330, 3950, 4680 |
1
We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!
Tags:
cables
, na2xs
, electroenergetic
, wind
, energy
, tele
, fonika
, kable
, NA2XS(F)2Y
, Electroenergetic cables
, Cables for wind energy