5-7 days
Modbus RTU or TCP to BACnet INBACMBM6000000 Gateway 600 points.
Integrate any Modbus RTU or TCP Slave device, or both at the same time, with a BACnet BMS or any BACnet IP or BACnet MS/TP controller. It fulfills B-AAC BACnet profile. BTL approved.
Specification:
Ports:
- Port A:
- 1x Serial EIA485 Plug-in screw terminal block (2 poles) A, B
- 1x Plug-in screw terminal block green (2 poles); SGND (Reference ground or shield); 1500VDC isolation from other ports
- Switch A:
- 1x DIP-Switch for serial EIA485 configuration:
- Position 1: ON: 120 Ω termination active/Off: 120 Ω termination inactive
- Position 2-3: ON: Polarization active/Off: Polarization inactive
- Port B:
- 1x Serial EIA232 (SUB-D9 male connector); Reserved for future use
- 1x Serial EIA485 Plug-in screw terminal block (3 poles); A, B, SGND (Reference ground or shield); 1500VDC isolation from other ports
- Switch B:
- 1x DIP-Switch for serial EIA485 configuration:
- Position 1: ON: 120 Ω termination active/Off: 120 Ω termination inactive
- Position 2-3: ON: Polarization active/Off: Polarization inactive
- Ethernet: 1x Ethernet 10/100 Mbps RJ45
Power:
- Connector: 1x Plug-in screw terminal block (3 poles)
- Input Voltage: 9 to 36VDC +/-10%, Max.: 140mA; 24VAC +/-10% 50-60Hz, Max.: 127mA; Recommended: 24VDC
LED indicators:
- 2x Run (Power)/Error
- 2x Ethernet Link/Speed
- 2x Port A TX/RX
- 2x Port B TX/RX
- 1x Button A indicator
- 1x Button B indicator
Mechanical Characteristics:
- Construction: Plastic, type PC (UL 94 V-0)
- Dimensions: 90mm x 88mm x 56mm
- Color: Light Grey. RAL 7035
- Protection: IP20 (IEC60529)
- Mounting:
- Wall
- DIN rail EN60715 TH35
Environmental Characteristics:
- Operation Temperature: 0°C to 60°C
- Humidity: 5% - 95%, non condensing
Warranty: 36 months
The INBACMBM6000000 old device code is IBOX-BAC-MBM
1
We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!
Tags:
bacnet
, modbus
, inbacmbm6000000
, intesis
, INBACMBM6000000
, to Modbus RTU
, to BACnet IP
, to Modbus RTU
, to BACnet MS/TP
, to Modbus TCP
, to BACnet IP
, to Modbus TCP
, to BACnet MS/TP