Menu
Your Cart

FJ-AC-MBS-1 (INMBSFGL001I000)

FJ-AC-MBS-1 (INMBSFGL001I000)
FJ-AC-MBS-1 (INMBSFGL001I000)
5-7 days
FJ-AC-MBS-1 (INMBSFGL001I000)
FJ-AC-MBS-1 (INMBSFGL001I000)
FJ-AC-MBS-1 (INMBSFGL001I000)
  • Stock: 5-7 days
  • Brand: Intesis
  • Model: FJ-AC-MBS-1
1 280,44 zł

Fujitsu RAC and VRF systems to Modbus RTU Interface (to CN connector).

The Fujitsu-Modbus gateway INMBSFGL001I000 allows fully bi-directional communication between Fujitsu RAC and VRF systems and Modbus RTU (RS-485) networks. The INMBSFGL001I000 is wired directly to an indoor unit. This allows not only the control of the main AC functions such as operating mode, fan speed, temperature setpoint…but the monitoring of errors, alarms and some internal variables.

The product can be installed and set up in a really short time. It’s only a matter of wiring the gateway to the AC unit and configure the DIP-SW accordingly. No configuration software and no power supply are required. The consistent Modbus register mapping used for all AC brands, helps improving the integration time of each project.

Features:

  • Modbus RTU (EIA485) slave device
  • Configuration from both onboard DIP-switches and Modbus RTU
  • Quick and easy installation (plug and set the DP-SW)
  • External power not required
  • Simultaneous control of the AC unit by the IR remote controller and by Modbus RTU
  • Reduced dimensions 93 x 53 x 58 mm
  • Mountable on DIN rail, wall, or even inside the indoor unit in some models of AC
  • Window contact function allows energy savings. Costs related to HVAC systems in a building are one of the highest and this type of functions allow to reduce them
  • Total control and monitoring of the AC unit from Modbus RTU, including AC unit’s internal variables, running hours counter (for filter maintenance control) and error indication

Specification:

  • Enclosure:
    • Plastic, type PC (UL 94 V-0)
    • Net dimensions (dxwxh): 93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”
    • Color: Light Grey. RAL 7035
  • Weight: 85 g
  • Mounting: Wall; DIN rail EN60715 TH35
  • Terminal Wiring (for low-voltage signals): For terminal: solid wires or stranded wires (twistedor with ferrule)
    • 1 core: 0.5mm2… 2.5mm2
    • 2 cores: 0.5mm2… 1.5mm2
    • 3 cores: not permitted
  • ModBus RTU port: 1 x EIA485 Plug-in screw terminal block (2 poles + GND) with 120 Ω resistor termination and polatization selectable by switch
  • AC unit port: 1 x Specific connector, Specific cable included
  • Switch 1(SW1): 1 x DIP-Switch for Air Conditioner Unit + ModBus baud rate
  • Switch 3 (SW3): 1 x DIP-Switch for ModBus RTU slave address + temperature magnitude (ºC/ºF) and scale (x1/x10)
  • Operation Temperature: 0ºC to 70ºC
  • Operational Humidity: <95% RH, non-condensing
  • Isolation voltage: 1500 VDC
  • Isolation resistance: 1000 MΩ
  • Protection: IP20
  • LED indicators: 2 x Onboard LED - Operational status

Warranty: 36 months