5-7 days
BACnet IP & MS/TP - PANASONIC AC ECOi and PACi Lines (PAC, VRF) 128 Indoor Units
The newer version of this device is IN771AIR00LO000
The INBACPAN128O000 Panasonic-BACnet gateway allows fully bi-directional communication between Panasonic ECOi and PACi Air Conditioner units and BACnet IP or MSTP networks.
The INBACPAN128O000 gateway is wired directly to an indoor unit. This allows not only the control of the main AC functions such as operating mode, fan speed, temperature setpoint…but the monitoring of errors, alarms and some internal variables. The product can be installed and set up in a really short time. It’s only a matter of wiring the gateway to the AC unit and configure the DIP-SW accordingly. No configuration software and no power supply are required. The product offers a web interface to easily monitor and control the indoor unit connected to the gateway. Additionally, the IP network settings can be stablished from this web interface.
Specification:
Ports:
- BACnet/IP port: 1x Ethernet 10Base-T (RJ45)
- CZ-CFUNC2 port: 1x EIA485, 2-pin plug-in screw terminal block
- Console port: EIA232, (DB9 female DCE); SELV; also allows configuration and upgrades firmware
Terminal wiring (for power supply and low-voltage signals):
- Per terminal: solid wires or stranded wires (twisted or with ferrule):
- 1 core: 0.5mm2...2.5mm2
- 2 cores: 0.5mm2...1.5mm2
- 3 cores: not permitted
Power:
- Connector: 2-pin plug-in terminal block
- Input Voltage: 9 to 30VDC +/-10%, Max.: 125mA; 24VAC +/-10% 50-60Hz, Max.: 127mA
- Must use a NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply
System Control & Monitoring:
- LED indicators:
- 1x Power
- 2x Ethernet port activity (LNK, ACT)
Mechanical Characteristics:
- Construction: Plastic, type PC (UL 94 V-0)
- Dimensions: 107mm x 105mm x 58mm
- Color: Light Grey
- Protection: IP20 (IEC60529)
- Mount:
- Wall
- DIN rail EN60715 TH35
Environmental Characteristics:
- Operation Temperature: 0°C to 70°C
- Humidity: 5% - 95%, non condensing
Certifications & Standards:
- CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC)
- EN 61000-6-2
- EN 61000-6-3
- EN 60950-1
- EN 50491-3
- RoHS conformity: Compliant with RoHS directive (2002/95/CE)
The INBACPAN128O000 old device code is PA-AC-BAC-16
Warranty: 36 months