Menu
Your Cart

LG VRF systems to Modbus Gateway - LG-AC-MBS EOL

LG VRF systems to Modbus Gateway - LG-AC-MBS EOL
LG VRF systems to Modbus Gateway - LG-AC-MBS EOL
5-7 days
LG VRF systems to Modbus Gateway - LG-AC-MBS EOL
LG VRF systems to Modbus Gateway - LG-AC-MBS EOL
LG VRF systems to Modbus Gateway - LG-AC-MBS EOL
  • Stock: 5-7 days
  • Model: LG-AC-MBS
0,00 zł

Available Options

A proven choice for industrial installations.
Ask for compatibility and model selection.
Register and get cheaper offers today.

Full design package: User manual, CE declaration, CAD, PDF, certificates and test reports

If you're preparing technical documentation or an installation design, you can receive a complete set of design materials for this model. This is a quick way to gather the required documents for audits, acceptance, or project documentation.

  • Device User Manual
  • CE Declaration of Conformity (EU Declaration of Conformity)
  • Mechanical DrawingsCAD (STEP/DWG) or high-quality PDF
  • Additional Certificates (if available for the model)
  • Test Reports (if available for the model)
Request a package: User manual, CE declaration, CAD, PDF, certificates, test reports

LG VRF systems to Modbus Gateway.

The IntesisBox Gateway has been specially designed to allow bidirectional control and monitoring of LG VRF solutions from a Modbus installation.

Specification:

Terminal wiring (for power supply and low-voltage signals)

  • Per terminal: solid wires or stranded wires (twisted or with ferrule):
    • 1 core: 0.5mm2 ~ 2.5mm2
    • 2 cores: 0.5mm2 ~ 1.5mm2
    • 3 cores: not permitted

Ports:

  • LG AC port: 1x EIA485. Plug-in screw terminal block (2 poles). SELV
  • Modbus RTU ports:
    • 1x Serial EIA232 (DB9 male DTE). SELV
    • 1x Serial EIA485 (Plug-in screw terminal block 2 poles). SELV
  • Modbus TCP port: 1x Ethernet 100Base-T RJ45
  • Console port: EIA232. DB9 female connector (DCE). SELV (also allows configuration and upgrades firmware)

Power:

  • Connector: 2-pin plug-in terminal block
  • Input Voltage: 9 to 30VDC +/-10%, Max.: 125mA; 24VAC +/-10% 50-60Hz, Max.: 127mA
  • Must use a NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply

System Control & Monitoring:

  • LED indicators:
    • 1x Power
    • 2x Serial port Modbus RTU activity (Tx, Rx)
    • 2x Serial port LG AC activity (Tx, Rx)
    • 2x Ethernet port Modbus TCP link and activity (LNK, ACT)

Mechanical Characteristics:

  • Construction: Plastic, type PC (UL 94 V-0)
  • Dimensions: 107mm x 105mm x 58mm
  • Color: Light Grey. RAL 7035
  • Mounting:
    • Wall
    • DIN rail EN60715 TH35

Environmental Characteristics:

  • Operation Temperature: 0°C to 70°C
  • Humidity: 5% to 95%, non condensing

Warranty: 12 months

Ordering Information:

  • LG-AC-MBS-4 - Modbus Server RTU & TCP - LG AC (RAC, PAC, VRF) 4 Indoor Units
  • LG-AC-MBS-8 - Modbus Server RTU & TCP - LG AC (RAC, PAC, VRF) 8 Indoor Units
  • LG-AC-MBS-32 - Modbus Server RTU & TCP - LG AC (RAC, PAC, VRF) 32 Indoor Units
  • LG-AC-MBS-64 - Modbus Server RTU & TCP - LG AC (RAC, PAC, VRF) 64 Indoor Units