M-7065BD CR
2-3 weeks
4-channel Isolated Digital Input and 5-channel DC SSR Output Module using the DCON and Modbus Protocols with LED Display.
The I-7063B module provides 8 digital input channels and 3 DC SSR output channels, and the I-7065B provides 4 digital input channels and 5 DC SSR output channels. All digital input channels can be used as 16-bit counters. In addition, the digital input channels can be selected either as sink- or source-type via wire connections. In comparison to electromechanical relays, SSR technology provides a faster response time and greater electrical endurance. The integration of DC SSR technology also eliminates potential for arcing, bounce, and switching noise.
The I-7063BD provides 11 LED indicators and the I-7065BD/M-7065BD provides 9 LED indicators that can be used to monitor the status of the digital input and SSR output. There are also options for configuring power-on and safe values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided to enhance noise protection capabilities in industrial environments. The M-7065B supports both the Modbus RTU and DCON protocols, which can be configured via software.
Features:
- 4 Digital Input channels and 5 DC SSR Output channels
- Form A DC Solid State Relay Output
- No Arcing, No Bounce, and No Switching Noise
- Sink- and Source-type for Digital Input
- Digital Input Channels can be used as 16-bit Counters
- Configurable Power-on Value Settings
- Configurable Safe Value Settings
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
- DIN rail mount
General technical parameters | |
I/O | 5x relay outputs, 4x digital inputs |
Protocol support | DCON, Modbus RTU |
Industrial grade | |
Optoisolation | 3750VDC |
Operating temperature | -25°C to 75°C |
Input voltage | 10~30VDC |
Mount | DIN rail, Wall mount |
1
We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!
Tags:
7065bd
, modbus
, dcon
, ethernet
, icpdas
, M-7065BD
, Modbus RTU (RS-485)
, DCON (RS-232/485