5-10 days
96W Single Output Industrial DIN Rail Power Supply.
DIN rail mounted power supply unit with 48VDC output voltage, 96W power, 2A output current and fanless cooling.
Features:
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- ZCS/ZVS technology to reduce power dissipation
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- DC OK relay contact
- 100% full load burn-in test
- No load power consumption < 1W
Specification:
Power supply
- Output:
- DC Voltage: 48V
- Rated Current: 2A
- Current Range: 0 ~ 2A
- Rated Power: 96W
- Ripple & Noise (max.): 200mVp-p
- Voltage Adj. Range: 48 ~ 56V
- Voltage tolerance: +/- 1.0%
- Line Regulation: +/- 1.0%
- Load Regulation: +/- 1.0%
- Setup, Rise Time: 3000ms, 50ms/230VAC; 3000ms, 50ms/115VAC at full load
- Hold up time (typical): 50ms/230VAC; 20ms/115VAC at full load
- Input:
- Voltage Range: 85 ~ 264VAC; 120 ~ 370VDC
- Frequency range: 47 ~ 63Hz
- Power Factor (typical): PF≧0.95/230VAC; PF≧0.98/115VAC at full load
- Efficiency (typical): 88%
- AC Current (typical): 1.3A/115VAC; 0.8A/230VAC
- In Rush Current (typical): Cold Start 30A/115VAC; 60A/230VAC
- Leakage Current: <1mA / 240VAC
Protection
- Overload: 105 ~ 150% rated output power
- Protection type: Constant current limiting, recovers automatically after fault condition is removed
- Over Voltage: 57.6 ~ 64.8V
- Protection type: Shut down o/p voltage, re-power on to recover
- Over Temperature: Shut down o/p voltage, auto-recovery or re-power on to recover
Function
- DC OK Active Signal: Relay contact rating (max.): 30V/1A resistive
Safety & EMC
- Safety Standards: UL508, TUV EN60950-1 approved
- Withstand Voltage: I/P-O/P:3KVAC; I/P-FG:2KVAC; O/P-FG:0.5KVAC
- Isolation Resistance: I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/25°C/70% RH
- EMC Emission: Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
- EMC Immunity: Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
Environmental Characteristics
- MTBF: 346.000 h
- Weight: 0,42 kg
- Dimensions (W x D x H): 55mm x 90mm x 100mm
- Operation Temperature: -10°C ~ 60°C (Refer to output load derating curve)
- Storage Temperature: -40°C ~ 85°C
- Humidity: 20% to 90% while working; 10% to 95% storage
- Vibration: Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
Warranty: 36 months
ORDERING INFORMATION: MDR-100-48
General technical parameters | |
Power | 96W |
Output current | 2A |
Output voltage | 48VDC |
Industrial grade | |
Operating temperature | -10°C to 60°C |
Input voltage | 85~264VAC, 120~370VDC |
Manufacturer's warranty | 36 months |
Mount | DIN rail |
We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!