INKNXHIT016O000 – Hitachi VRF to KNX Gateway for 16 units with H-Link and Intesis MAPS

INKNXHIT016O000 is Hitachi VRF systems to KNX Gateway for 16 indoor units.

Hitachi to KNX Gateway – Model INKNXHIT016O000 for VRF Integration | Intesis by HMS
5-7 days
INKNXHIT016O000 – Hitachi VRF to KNX Gateway for 16 units with H-Link and Intesis MAPS
  • Stock: 5-7 days
  • Model: INKNXHIT016O000
0.00 zł
A proven choice for industrial installations.
Ask for compatibility and model selection.
Additional discounts for registered customers.

Full design package: User manual, CE declaration, CAD, PDF, certificates and test reports

If you're preparing technical documentation or an installation design, you can receive a complete set of design materials for this model. This is a quick way to gather the required documents for audits, acceptance, or project documentation.

  • Device User Manual
  • CE Declaration of Conformity (EU Declaration of Conformity)
  • Mechanical DrawingsCAD (STEP/DWG) or high-quality PDF
  • Additional Certificates and Test Reports (if available for the model)
Request a package: User manual, CE declaration, CAD, PDF, certificates, test reports

Hitachi VRF systems to KNX Gateway for 16 indoor units. 

The newer version of this device is IN770AIR00SO000 

The INKNXHIT016O000 IntesisBox gateway has been engineered to enable seamless, bidirectional integration between Hitachi VRF air conditioning systems and KNX-based building automation environments. Designed for professional installations, it supports up to 16 indoor units, making it ideal for small and medium-sized commercial or residential applications.

Direct connection to the outdoor unit’s communication bus (H-Link) enables real-time control of all connected indoor units. Users can adjust temperature, mode, fan speed, and other key AC functions through their KNX system. Additionally, the interface allows access to internal variables of the outdoor units, enabling deeper system diagnostics and energy-efficient control strategies.

Device setup is handled via Intesis® MAPS, a versatile and user-friendly configuration tool from HMS. MAPS allows integrators to scan connected units automatically, assign group addresses, test functionality, and analyze data in both online and offline modes. Its powerful diagnostics help identify communication issues and ensure a fast commissioning process.

Specification:

Ports:

  • Port A:
    • 1x KNX TP-1 (orange, 2 poles); 2500VDC isolation; KNX current: 5mA; Voltage: 29VDC
    • 1x Green terminal (2 poles); Reserved for future use
  • Switch A: 1x DIP-Switch for PORT A – Reserved
  • Port B:
    • 1x Serial EIA232 (SUB-D9 male); Reserved
    • 1x H-Link terminal (3 poles); 1500VDC isolation
  • Switch B: 1x DIP-Switch for PORT B – Reserved (default OFF)
  • 1x Ethernet RJ45 10/100 Mbps

Power:

  • Connector: Plug-in screw terminal block (3 poles)
  • Input Voltage: 9–36VDC ±10%, max 140mA; 24VAC ±10% 50–60Hz, max 127mA
  • Recommended supply: 24VDC

LED indicators:

  • 2x Run/Power & Error
  • 2x Ethernet Link & Speed
  • 2x Port A TX/RX
  • 2x Port B TX/RX
  • 1x Button A indicator
  • 1x Button B indicator

Mechanical characteristics:

  • Construction: Plastic, PC type (UL 94 V-0)
  • Dimensions: 90 x 88 x 56 mm
  • Color: Light Grey (RAL 7035)
  • Protection rating: IP20 (IEC60529)
  • Mounting: Wall or DIN rail (EN60715 TH35)

Environmental characteristics:

  • Operating temperature: 0°C to 60°C
  • Humidity: 5%–95%, non-condensing

Warranty: 36 months

Old product code: HI-AC-KNX

  • INKNXHIT016O000 – for 16 indoor units
  • INKNXHIT064O000 – for 64 indoor units

Application diagram of the INKNXHIT016O000 communication module