Menu
Your Cart

RMT-101

RMT-101
2-3 days

Relay control the maximum current.

RMT-101 designed to permanent control of active value current of single-phase load in 0 to 100A range,and to turn OFF it in case of excess of user adjusted maximum allowed load current (with independent timelag) with preset cut-OFF time and subsequent automatic insertion with preset turn-ON time or with block ofreclosing.Current sitting, reaction time of relay and autoreclosing time are adjusted by user using potentiometers onthe front panel of RMT-101. Measurement is carried out by built-in current sensor without break of electrical circuit.

RMT-101 can be used as:

  • digital ammeter;
  • limit relay input current;
  • selection relay (to select of priority load).
In RMT-101 for current measuring it is used Built-in current transformer. RMT-101 allows controllingcurrent values and condition of load per LED indicators on the front panel.


General technical characteristic of RMT-101


Operation supply voltage, V: 220/240

Operation voltage range at which RMT-101 will keep working, V *: 130 to 300

Power frequency Hz: 47 − 53

Current measurement range, А: 0-100

Measurement inaccuracy, no worse than: 1%

Adjustment range:

а) Imax: 0 − 1

А absolute measurement accuracy of current, A, no more than: 0 ±0,04

b) Imax: 0-99,9

A absolute measurement accuracy of current, A, no more than: ±0,4

Adjustment range of ton, sec: 0 − 900, ∞

Adjustment range of toff, sec: 0 − 300

Readiness time, sec, no more than: 0,5

Power consumption (under load), VA, no more than: 3,0

Commutation overcurrent of the output contacts at cosφ=1, А: 8

Commutation life of the output contacts:

- under 5A power load, times, no less then: 100 000

- under 1A power load, times, no less then: 1 000 000

Protection class of:

- Device: IP40

- Connection terminal: IP20

Operational temperature range, °С from: -25 to +55

Storage temperature, °С from: -45 to +70

Weight , kg, no more than: 0,200

Outer dimensions, 2 S-modules for 35mm DIN-rail, mm: :

Mounting to standard: :

Positioning: :


* Indicator switching-off (poz.10, fig. 1) is provided at supply voltage decrease more low 120 voltand blocking of functioning RМТ-101 at a supply voltage reduction more low 100 volt.


Industrial grade
IP rating IP20, IP40
Operating temperature -25°C to 55°C
Input voltage 130~300VAC
Mount DIN rail