Multi-conductor cables with insulation and sheath made of heat-resistant silicone rubber, for mobile and portable receivers.
Designed to work in conditions of very high temperature or very low ambient temperature, especially for installation in shipbuilding, steel mills, steelworks, cement plants and power plants and for connecting lamps used in industrial installations, provided that a mechanical cover is used, in dry, humid and wet rooms as well as in the open air, as a movable connection cable at low mechanical loads.
They do not contain halogens, have a high flash point, very good dielectric properties at elevated temperatures, high resistance to many chemicals (oxygen, ozone, vegetable and animal fats, vegetable oils, soap solutions, alcohols, ammonia, weak alkalis and acids, sea water).
Construction:
- Cores: Copper tinned round multi-core class 5 according to PN-EN 60228
- Insulation: EI2 silicone rubber
- Coating: Silicone rubber type EM9
- Insulation color (acc. to PN-HD 308 S2):
- 2-core: blue, brown
- 3-core: green-yellow, blue, brown
- 4-core: green-yellow, brown, black, gray
- 5-core: green-yellow, blue, brown, black, gray
Characteristics:
- Maximum conductor temperature during cable operation: +180°C
- Minimum ambient temperature for permanently laid cables: -60°C
- Minimum ambient temperature for cable laying: -25°C
- Maximum core temperature during short circuit: +350°C
- Maximum permissible load: 15 N per mm² of copper cross-section
- Test voltage 50 Hz: 2000V
- Resistance to flame spread: PN-EN 60332-1-2
- Standard packaging: in reels of 50 or 100 m and on drums of 500 m. There is a possibility of offering other lengths of sections and types of packaging
Complies with: PN-EN 50525-2-83
Industrial grade | |
Operating temperature | to 180°C |
Cable parameters | |
Minimum bending radius | 3D, 4D, 5D, 6D |
Core | Copper |
Insulation | Silicone rubber |
Maximum short circuit temperature | 350°C |
Test voltage | 2 kV |
Standard packaging | Discs, On drums |
Coating | Silicone rubber |
Minimum ambient temperature | -60°C |
Resistance to flame spread | EN 60332-1-2 |
Number of wires in the cable | Multi-core |
Working conductor cross section [mm2] | 0.5, 0.75, 1.0, 1.5, 2.5, 4.0, 6.0 |