To be confirmed
NHXMH 300/500V (N)HXMH 300/500V
- Stock: To be confirmed
- Brand: TELE-FONIKA Kable
- Model: NHXMH 300/500V (N)HXMH 300/500V
0,00 zł
Installation cables with XLPE insulation and halogen-free plastic coating.
Installation cables with crosslinked polyethylene insulation and a sheath of halogen-free thermoplastic material, with low fumes and corrosive gases emission during combustion. Designed for installation in buildings with stricter fire protection requirements. Designed for permanent installation in power and lighting installations, for laying in dry and damp rooms above, under and under plaster, in masonry and concrete, except for direct deposition in single-fraction concrete, vibrated and whipped concrete.
Construction:
- Core: Made of soft copper wires, single-core class 1 or multi-wire class 2 according to EN 60228
- Insulation: cross-linked polyethylene XLPE type 2Xl1 according to DIN VDE 0276-604
- Filling: halogen-free unvulcanized rubber
- Coating: Special Halogen free thermoplastic HM2 according to DIN VDE 0250-214
- Coating color: gray RAL 7035, white or red. Other colors available on request
- Colors of insulation:
- NHXMH-J:
- 1-core: green-yellow
- 3-core: green-yellow, blue, brown
- 4-core: green-yellow, brown, black, gray
- 4-core for specific applications: green-yellow, blue, brown, black
- 5-core: green-yellow, blue, brown, black, gray
- 7 and more cores: green-yellow, black remaining wires digitally printed
- NHXMH-O:
- 1-core: black
- 2-core: blue, brown
- 3-core: brown, black, gray
- 3-core for specific applications: blue, brown, black
- 4-core: blue, brown, black, gray
- 4-core for specific applications: blue, brown, black, gray, black
- 5-core: black with digital print
Characteristics:
- Maximum temperature of the vein during cable operation: +70°C
- The minimum ambient temperature for permanently laid cables: -30°C
- The minimum ambient temperature when laying cables: -5°C
- Maximum core temperature during short circuit: +250°C
- The minimum bending radius:
- 10 x D single-core cables
- 6 x D multi-core cables
- D - outer diameter of the cable
- Test voltage 50 Hz: 2000V
- Packaging: In reels or cable drums
Reaction to fire:
- Resistance to flame spread: IEC 60332-1-2, IEC 60332-3-24 (SS 4241475 F4C), IEC 60332-3-23 (SS 4241475 F4B)
- Smoke emission during combustion: DIN EN 61034-2, IEC 61034-2
- Separation of corrosive gases during combustion:
- IEC 60754-1, IEC 60754-2, DIN EN 50267-2-2: pH ≥ 4,3
- conductivity ≤ 100 μS/cm
- CPR - reaction to fire class (according to EN 50575): B2ca-s1a, d0, a1
Complies with: DIN VDE 0250-214
Industrial grade | |
Operating temperature | to 70°C |
Cable parameters | |
Minimum bending radius | 10D, 6D |
Core | Copper |
Insulation | XLPE |
Installation temperature | -5°C to 70°C |
Maximum short circuit temperature | 250°C |
Test voltage | 2 kV |
Coating | Thermoplastic halogen-free compound |
Filling | Halogen-free unvulcanized rubber |
Minimum ambient temperature | -30°C |
Resistance to flame spread | IEC 60332-1-2, IEC 60332-3-24, IEC 60332-3-23 |
Fume emission during combustion | DIN EN 61034-2, IEC 61034-2 |
Outer diameter [mm] | 5.1, 5.4, 6.0, 6.5, 7.5, 7.7, 8.1, 8.5, 8.7, 8.9, 9.4, 9.6, 9.8, 10.1, 10.3, 10.4, 10.8, 11.6, 11.8, 12.6, 12.8, 13.3, 13.9, 14.0, 15.3, 16.0, 16.8, 17.0, 18.6, 19.4, 20.7, 21.0, 23.3, 23.7, 25.5, 26.0, 28.6 |
Cable weight [kg/km] | 40, 51, 68, 89, 94, 109, 123, 130, 132, 146, 153, 173, 176, 189, 210, 226, 265, 275, 289, 318, 354, 357, 426, 443, 539, 547, 668, 675, 814, 837, 1040, 1044, 1312, 1398, 1601, 1753, 2133 |
Working conductor cross section [mm2] | 1.5, 2.5, 4.0, 6.0, 10.0, 16.0, 25.0, 35.0 |
1
We know that choosing the right product can be difficult. Get a free consultation with a technical expert and make the right decision!