Miner tire unground wires with insulation and rubber tire for rated voltage 0.6 / 1 kV.

Construction:

  • Veins:
    • Multi-wire copper according to PN-88 / E-90160
    • Class 5 workplace
    • Protective class 5c (tin plated)
  • Separator: On working conductors made of polyester film or paper
  • Insulation: On working conductors made of heat-resistant rubber type IEP with properties according to PN-89 / E-29100
  • The color of the insulation of the veins: Working - natural, red, green
  • A protective vein separated in three parts: Each part was in conductive rubber type GP with properties according to PN-89 / E-29100 black, corrugated surface
  • Wire center: Filled with inserts and wrapped with conductive tape
  • Tire: Made of ON4 type tire rubber with properties according to PN-89 / E-29100
  • Tire color: Black or other - after agreement with the customer

Characteristic:

  • Application: For connecting mobile and portable devices in mining plants
  • Explanation of the letter symbol of the wire: OnGc-G - power cable with copper conductors with heat-resistant rubber insulation (Gc) and rubber tire resistant to flame spread (On) - mining (G) with strands twisted into the center on the core
  • Example of wire marking: OnGc-G - OnGc-G wire, 4-wire, 0.6 / 1 kV, 70 mm2 core wire, 25 mm2 protective conductor: OnGc-G 3x70 + 3x25 / 3 mm2 0.6 / 1 kV cable, ZN- 95 / MP-13-K101
  • Maximum core temperature during cable operation: + 90 °C
  • The smallest possible bending radius:
    • For permanent installation of 6D
    • For 10D mobile receivers
    • D - diameter of the wire
  • Assay voltage: 3.2 kV
  • Packing: On drums

Compliant with: ZN-95 / MP-13-K 101

Certificates: EMAG


Industrial grade
Operating temperature to 90°C
Cable parameters
Minimum bending radius 6D, 10D
Core Copper
Insulation Heat-resistant rubber
Test voltage 3.2 kV
Standard packaging On drums
Tire Rubber
Number of wires in the cable Multi-core
Outer diameter [mm] 25.7, 32.0, 36.2, 41.5, 45.5, 51.8, 58.8
Cable weight [kg/km] 1160, 1670, 2180, 2990, 3815, 4900, 6050
Working conductor cross section [mm2] 16.0, 25.0, 35.0, 50.0, 70.0, 95.0, 120.0