Menu
Your Cart

NA2XY-J,O 0,6/1kV, (N)A2XY-J,O 0,6/1kV

NA2XY-J,O 0,6/1kV, (N)A2XY-J,O 0,6/1kV
To be confirmed
NA2XY-J,O 0,6/1kV, (N)A2XY-J,O 0,6/1kV
  • Stock: To be confirmed
  • Brand: TELE-FONIKA Kable
  • Model: NA2XY-J,O 0,6/1kV, (N)A2XY-J,O 0,6/1kV
Product Views: 6742
0,00 €

Power cables with aluminum wires, XLPE insulation and PVC coating.

PVC insulated and sheathed cables for the transmission of electricity. Designed for installation in the air, in the ground, under water, inside buildings and in cable ducts.

Construction:

  • Cores: Aluminum, round class 1 (RE) or round, round compressed class 2 (RM) or sector solid one (SE) or sectoral multi-wire class (SM) according to EN 60228
  • Insulation: A special DIX3 XLPE compound according to HD 603.1
  • Inner coating: Filling mixture
  • Outer shell: Special DMV5 PVC blend according to HD 603.1
  • Coating color: black
  • Identification of veins:
    • NA2XY-J:
      • 1-wire: yellow-green
      • 2-wire: yellow-green, black
      • 3-wire: yellow-green, blue, brown
      • 4-wire: yellow-green, brown, black, gray
      • 4-wire for specific applications: yellow-green, blue, brown, black
      • 5-wire: yellow-green, blue, brown, black, gray
    • NA2XY-O:
      • 1-wire: black
      • 2-wire: blue, brown
      • 3-wire: brown, black, gray
      • 3-wire for specific applications: blue, brown, black
      • 4-wire: blue, brown, black, gray
      • 5-wire: blue, brown, black, gray, black

Characteristic:

  • Maximum temperature during cable operation: + 90 °C
  • Minimum ambient temperature for permanently laid cables: -30 °C
  • The minimum ambient temperature for cable laying: -5 °C
  • Maximum core temperature during short circuit: + 250 °C
  • Minimum bending radius: 15 x D for single-core cables, 12 x D for multi-core cables, D - cable diameter
  • Maximum allowable tensile stresses: 30 N / mm
  • Test voltage AC 50Hz 5min: 4kV
  • Standard packaging: 1000m on drums. It is possible to offer other lengths and types of packaging

Reaction to fire:

  • Flame spread resistance: IEC 60332-1-2
  • CPR - reaction to fire class (according to EN 50575): Eca

Compliant with: VDE 0276-603, VDE 0276-627, HD 603 S1, HD 627 S1, IEC 60502-1


Industrial grade
Operating temperature to 90°C
Cable parameters
Minimum bending radius 15D, 12D
Core Aluminium
Insulation XLPE
Installation temperature -5°C to 90°C
Maximum short circuit temperature 250°C
Test voltage 4 kV
Coating Polyvinyl chloride (PVC)
Minimum ambient temperature -30°C
Resistance to flame spread IEC 60332-1-2
Number of wires in the cable Single-core, Multi-core
Outer diameter [mm] 9.6, 9.9, 11.1, 11.5, 12.1, 12.6, 13.4, 14.1, 15.7, 17.0, 17.5, 17.6, 17.9, 18.4, 18.5, 18.9, 19.4, 20.1, 20.2, 21.0, 21.3, 21.9, 22.2, 23.0, 23.2, 23.5, 24.2, 24.4, 24.7, 25.2, 25.3, 25.6, 26.4, 26.9, 27.5, 27.6, 27.7, 28.0, 28.5, 29.1, 30.3, 30.5, 30.9, 31.3, 31.6, 32.2, 33.4, 34.1, 34.3, 34.6, 34.9, 35.8, 36.8, 37.8, 38.4, 38.7, 39.0, 39.4, 40.1, 40.5, 42.1, 42.4, 42.5, 43.0, 43.5, 44.2, 44.4, 45.2, 45.5, 46.5, 46.6, 48.2, 48.3, 48.5, 48.8, 49.1, 50.6, 51.7, 52.6, 52.9, 53.8, 54.9, 56.3, 58.0, 58.2, 58.9, 59.9
Cable weight [kg/km] 119, 124, 162, 169, 199, 206, 255, 256, 334, 390, 413, 425, 434, 456, 503, 508, 509, 529, 554, 590, 619, 620, 623, 682, 736, 752, 754, 764, 768, 799, 857, 860, 904, 909, 928, 936, 938, 976, 1020, 1044, 1072, 1104, 1126, 1213, 1234, 1331, 1335, 1402, 1410, 1420, 1512, 1638, 1641, 1711, 1734, 1785, 1802, 2004, 2013, 2017, 2131, 2136, 2214, 2244, 2269, 2428, 2459, 2605, 2613, 2658, 2664, 2741, 2868, 3003, 3014, 3137, 3186, 3219, 3312, 3348, 3349, 3355, 3735, 3842, 4052, 4056, 4131, 4294, 4423, 4692, 4727, 5158, 5208

Write a review

Note: HTML is not translated!
Bad Good
We use cookies to offer you the best experience on our site. By continuing to browse the site, You are agree to use cookies.