Menu
Your Cart

INMBSBAC1000000 – Industrial BACnet IP/MS/TP to Modbus RTU/TCP Gateway, 100 Points

INMBSBAC1000000 – Industrial BACnet to Modbus RTU/TCP Gateway 100 Points | Intesis
3 year warranty Quantity discount 5-7 days
INMBSBAC1000000 – Industrial BACnet IP/MS/TP to Modbus RTU/TCP Gateway, 100 Points
  • Stock: 5-7 days
  • Brand: Intesis
  • Model: INMBSBAC1000000
3 097,30 zł
2 pieces or more 2 942,44 zł
5 pieces or more 2 880,49 zł
10 pieces or more 2 787,57 zł
26 pieces or more 2 632,71 zł
51 pieces or more 2 353,95 zł

INMBSBAC1000000 – BACnet IP & MS/TP to Modbus TCP & RTU Integration Gateway – 100 Points. 

The INMBSBAC1000000 gateway enables seamless bidirectional communication between BACnet IP/MS/TP devices and Modbus RTU/TCP systems. Designed for industrial automation and building management applications, this device supports the integration of up to 100 data points between both protocols, allowing data exchange as if all devices were part of the same native system.

Thanks to its onboard support for both Modbus TCP and Modbus RTU (simultaneously), the gateway ensures maximum flexibility for integration with PLCs, SCADA systems, or BMS controllers. On the BACnet side, both BACnet/IP and BACnet MS/TP servers can be connected. Configuration is managed using Intesis MAPS, a graphical tool that simplifies device setup and enables users to download or import custom project templates.

The built-in BACnet Explorer allows automatic scanning of BACnet networks and discovery of connected devices, significantly speeding up configuration. Data point mapping and formatting options are fully customizable, including scaling, data types, and byte order. Once deployed, the gateway functions as a reliable and efficient protocol bridge for real-time control and monitoring.

Certified with UL and BTL marks, and compliant with CE and RoHS directives, the INMBSBAC1000000 is suitable for mission-critical installations. Its compact, durable plastic housing with IP20 protection is ideal for mounting in control panels or switchboards via DIN rail or wall installation.

Key Features:

  • BTL and UL certified
  • Supports Modbus RTU (RS232/RS485) and Modbus TCP simultaneously
  • Compatible with BACnet IP and BACnet MS/TP
  • BACnet Explorer for automatic device detection
  • Intesis MAPS for easy integration and firmware updates
  • Up to 100 configurable points

Technical Specifications:

Ports:

  • 1x RS232 (DB9 male DTE)
  • 1x RS485 (2-pin screw terminal)
  • 1x Ethernet 10BT RJ45 for Modbus TCP & BACnet IP
  • 1x Console port: RS232 DB9 female (DCE)

Power:

  • Connector: 2-pin screw terminal
  • Input voltage: 9–30 VDC ±10%, 1.4 W / 24 VAC ±10%, 1.4 VA

Monitoring:

  • LEDs: Power, Modbus RTU Tx/Rx, Ethernet Link/Activity

Mechanical:

  • Enclosure: Plastic, PC (UL 94 V-0)
  • Dimensions: 107 × 105 × 58 mm
  • Color: Light Grey (RAL 7035)
  • Mounting: Wall or DIN rail (EN60715 TH35)
  • Protection: IP20 (IEC60529)

Environmental:

  • Operating temperature: 0°C to 70°C
  • Humidity: 5% to 90%, non-condensing

Certifications:

  • CE
  • RoHS compliant (Directive 2002/95/CE)

Warranty: 36 months

INMBSBAC1000000 – Industrial BACnet to Modbus RTU/TCP Gateway 100 Points | Intesis

Need assistance? Contact our expert: https://consteel-electronics.com/contact-us

General technical parameters
Ethernet 1x 10/100BaseT(X)
Serial port 1x RS-232, 1x RS-485
Industrial grade
Casing Plastic
IP rating IP20
Input voltage 9~30VDC, 24VAC
Mount Wall-mount, DIN rail